← All regulations
◆ Protected standard · description only
UNI EN 13501-1:2019

Fire classification of construction products and building elements - Part 1: Reaction to fire

In forceSicurezza in caso d'incendioProdotti & Marcatura CENorma tecnica (UNI/EN/ISO)Volontaria● Verified

Summary

TAV. 00

Defines the reaction-to-fire classification procedure for construction products via the Euroclasses (A1, A2, B, C, D, E, F), supplemented by additional classes for smoke production (s1-s3) and flaming droplets (d0-d2). Floorings and linear pipe insulation have their own classes. It is the reference for CE marking on reaction to fire.

Scope of application

TAV. 01

Applies to construction products and building elements that must declare their reaction to fire (e.g. for CE marking). It provides the common European classification language referenced by national fire-safety rules (e.g. the Fire Prevention Code). The class system, within the European construction products regulation, is set by Delegated Regulation (EU) 2016/364.

How this standard works

TAV. C

The standard orders products on a descending scale of Euroclasses, from the material that does not contribute to fire to the one that does not even reach class E, and adds two sub-classifications describing smoke production and flaming droplets. Floorings and linear pipe insulation have scales of their own. We describe its logic here — without reproducing tables or values, which remain protected content of the standard.

Understanding how this standard is built means understanding a language that recurs throughout fire safety: the Euroclasses. They are the standardised way, valid across the European Union, of stating how much a material contributes to a fire.

The reaction-to-fire Euroclasses
A1
A2
B
C
D
E
F
← non-combustibledoes not reach class E →

One letter is not enough: the two sub-classes

The main class (the letter) tells only part of the story. For materials from A2 to D, the standard also requires declaring two behaviours that can be decisive in a real fire: how much smoke they produce and whether they release flaming droplets. These are the sub-classes s (smoke) and d (droplets).

The two sub-classes (descriptive summary)
SymbolWhat it describesLogic
s1 → s3Smoke productionfrom low (s1) to high (s3)
d0 → d2Flaming dropletsfrom none (d0) to significant (d2)
Editorial summary for information: the exact assignment criteria are protected content of the standard.

Class F, since 2016

The class system, within the European construction products regulation, is set by Delegated Regulation (EU) 2016/364, which repealed and replaced Decision 2000/147/EC. The change that matters is class F. It used to mean «reaction not determined»; since 2016 it is the class of products that do not reach the performance of class E. Whoever does not declare a product's reaction to fire uses instead the wording «no performance determined», provided by the construction products regulation for the declaration of performance.

Floorings, pipe insulation and cables

Floorings have their own classes, with the subscript fl (A1fl to Ffl), and for them the additional classification covers smoke only. Linear products for the thermal insulation of pipes also have their own classes, with the subscript L, and the same two additional classifications as other products, smoke and droplets. Electrical cables have a table of their own in the delegated regulation, with the subscript ca and one more additional classification, acidity.

Reaction and resistance: two standards, one system

Reaction to fire (this standard) measures how much a material contributes to the fire; fire resistance — classified by UNI EN 13501-2 — measures how long an element withstands it. The two standards are complementary: together they provide the full vocabulary with which fire-safety rules set requirements.

Key points

TAV. K
  • Euroclasses from A1 to F; since 2016 F denotes products that do not reach class E
  • Additional classes: smoke production s1-s3, flaming droplets d0-d2
  • Harmonised basis for CE marking (reaction to fire) of products
  • Pairs with UNI EN 13501-2 (fire resistance): reaction + resistance

Materials concerned

TAV. M

Building systems that apply it

TAV. S

Frequently asked questions

TAV. Q
What is the difference between reaction to fire and resistance to fire?

Reaction to fire (this standard) measures how much a material contributes to a fire — a property of the product. Resistance to fire instead measures how long an element keeps performing (load-bearing, compartmentation) during a fire, and is classified by other standards (R, E, I criteria).

Is an A1 material always required?

No. The required class depends on the application and is set by the fire-safety rules (e.g. the Fire Prevention Code) for that specific use, not by this standard. This standard only provides the classification language; it does not impose which class to use.

Why are some letters followed by codes like s1, d0?

Because the main class alone is not enough: smoke and flaming droplets matter in a real fire. The additional sub-classes (s for smoke, d for droplets) complete the classification for the relevant classes.

Is reaction to fire alone enough to ensure fire safety?

No: it is one of the measures. Fire-safety rules (e.g. the Fire Prevention Code) combine it with fire resistance, evacuation, detection and other measures. The reaction class concerns the product, not the whole building.

What does class F mean?

Since 2016 it is the class of products that do not reach the performance of class E (Delegated Regulation (EU) 2016/364). Before, under Decision 2000/147/EC, it meant «reaction not determined». Whoever does not declare a product's reaction to fire uses instead the wording «no performance determined».

Is a flooring classified like a wall finish?

No: floorings have their own classes, A1fl to Ffl, and for them the additional classification covers smoke only, not droplets (Delegated Regulation (EU) 2016/364, table 2).

Glossary

TAV. G
Euroclasse
The European reaction-to-fire class of a product, from A1 to F; since 2016 F is given to products that do not reach class E (Delegated Regulation (EU) 2016/364).
Reazione al fuoco
The behaviour of a material that, by decomposing, contributes to the fire it is exposed to.
Marcatura CE
The marking by which a construction product declares its performance against a harmonised standard, including reaction to fire.
Produzione di fumo (s)
Sub-class (s1-s3) expressing how much smoke a product develops during combustion, from low (s1) to high (s3).
Gocciolamento ardente (d)
Sub-class (d0-d2) expressing the release of flaming droplets or particles, from none (d0) to significant (d2).
Nessuna prestazione determinata
Wording by which the manufacturer, in the declaration of performance, does not declare a characteristic of the product (Regulation (EU) 305/2011, art. 6(3)(f)). It does not coincide with class F.
Classi fl
The reaction-to-fire classes of floorings, A1fl to Ffl, with smoke as the only additional classification.